No inverter is 100% efficient.

All Inverters (& Filters) generate heat,
when mounted in a control panel this has to be considered
when calculating the size of panel,
and considering the need for additional cooling.

The following tables give the typical amounts of heat loss:

Meiden VT230 & GE VAT2000 Drives.

200V Units

 

400V Units

Rating

(kW)

Power loss

Drive (W)

Power loss

Filter (W)

Power loss

Total (W)

 

Rating

(kW)

Power loss

Drive (W)

Power loss

Filter (W)

Power loss

Total (W)

0.75

62

6

68

0.75

83

1

84

1.5

84

7

91

1.5

111

2

113

2.2

117

13

130

2.2

129

6

135

4.0

153

25

178

4.0

175

13

188

5.5

215

28

243

5.5

275

8

283

7.5

301

50

351

7.5

345

8

353

11

420

90

510

11

369

22

391

15

506

90

596

15

481

45

526

18.5

708

90

798

18.5

550

50

600

22

757

90

847

22

675

37

712

30

1032

42

1074

30

876

83

950

37

1341

44

1385

37

1080

23

1103

45

1657

96

1753

45

1104

50

1154

55

2031

112

2143

55

1437

61

1498

75

2973

129

3102

75

2091

43

2134

 

     

90

2473

95

2568

 

   

 

110

2998

112

3110

 

   

 

132

3758

129

3887

 

   

 

160

4637

152

4789

 

   

 

200

5566

79

5645

 

   

 

250

7266

101

7367

 

   

 

315

8745

135

8880

GE VAT20 Drives.

VAT20

Model

Power loss

(W)

U20N0K2S

21

U20N0K4S

38

U20N0K7S

60

U20N1K5S

104

U20N2K2S

150

U20X0K7S

61

U20X1K5S

79

U20X2K2S

95

 

Download Panel Cooling Calculator (requires Microsoft Excel)

 

           

 