Safety InstructionsThe Purchaser/user is to comply with
the instructions and information The apparatus supplied could, when
energised, constitute a safety hazard HazardsThe equipment may operate at dangerous voltages and produce high temperatures when in operation. The unit is fitted with labels to warn of these hazards. Installation
Correct
installation A free-air flow environment is required around the resistor enclosure. The minimum recommended clearance to other equipment is 250mm. Particular attention should be paid to the clearance above the unit, as the exit air above the unit may be dangerously hot during operation. As both the issuing air temperature and the enclosure surface temperature are likely to exceed 100°C the ventilation holes in the enclosure must not be obstructed. In particular no combustible materials must come into contact with or be in close proximity to the top cover or the sides of the enclosure. Two or three tier enclosures can only be mounted in a horizontal position. Where canopies are fitted these must be fitted uppermost. On drives <=7.5kW an internal brake resistor may be fitted, this Must Be Disconnected when external brake resistors are used. Installation Procedure1) Identify suitable mounting surface in accordance with the requirements given. 2) Remove top cover giving access to mounting holes in base plate. 3) Secure unit to mounting surface using suitable fastenings. WiringOne Dynamic Braking Resistor (DBR) unit may be supplied as single or multiple enclosures, resistors in multiple enclosures should be connected in parallel All enclosures are fitted with over temperature sensors, which should be connected to the EMS input on the inverter, sensors in multiple enclosures should be connected in series.
Cable access can be facilitated via cable knock-outs (single-tier units) or un-drilled gland plate (two or three tier units). Notes 1) Resistor is not polarity sensitive. 2) Before operation ensure all electrical connections (including earth) are tight 3) Ensure that the top ventilation cover is free from obstruction. 4) If multiple enclosures are used, ensure correct connection by verifying the final resistance value is within ±10% of the required value 5) If resistors are mounted within an enclosure measures must be taken (fans / cooling) to dispose of the heat generated. MaintenanceThe equipment must be completely isolated from any power supply before any maintenance is carried out. Very little maintenance is required on this equipment, but maintenance inspections should be carried out at regular periods to ensure that the equipment is kept in a good and reliable condition. During maintenance inspections check that all connections are tight and the ventilation covers of the enclosure are free from any obstruction and as dirt-free as possible, and the danger labels on the exterior of the enclosure are kept in position and clean. |
|
|
|